Fireclass 557.202.080FC TLI800EN EN54 Approved Network Card
- Part Number: 557.202.080FC
- Categories: Ancillary (Addressable Fire Alarm Equipment)
- £491.37 (£589.64 inc VAT)
Fireclass 557.202.080FC TLI800EN EN54 Approved Network Card
The use of the FireClass Network allows the fragmentation of a number of fire controllers to be drawn into a network system.
The Fireclass Net communications network comprises a collection of network interface modules and peripheral equipment that together form a fault resistant and flexible peer-to-peer network for the Fireclass Digital addressable fire systems controllers.
One TLI800EN is required per FireClass and is installed onto the FireClass Main Processor board.
The TLI800EN is used to:
- Connect up to 24 Fireclass panels or other nodes to a single network
- Connect the Emergency display used to display an alarm in case of a System fault
Supported network communications media:
- Shielded twisted pair copper cable (RS485 standard)
- Fibre optic cable (multimode 50/125m or 62.5/125 m)
Key Features
- All field wiring terminations connect via removable terminal blocks
- Two RS-485 connections for twisted pair network communications
- Earth fault detection and isolation
- Onboard diagnostic LEDs. These indicate network communications activity and TLI800EN module faults
- Two Micro Controller Units. One is used as a backup microprocessor. These provide MCU fault detection and Emergency Mode fire alarm monitoring in the case of MCU failure
- Fire Alarm input, Fire Alarm output, and RS-485 Emergency Display connections for use in Emergency Mode