Categories

Site Links

  • Ziton Dual IR in Zinc Alloy Housing (FF742)

Ziton Dual IR in Zinc Alloy Housing (FF742)

Ziton Dual IR in Zinc Alloy Housing (FF742)
Brand: Ziton

Please note: This product is now obsolete, please contact us for further information.

Owing to present delivery delays from the OEM of this product, please see alternative equipment below for your consideration with regard to your on-going Projects:

Spectrex SharpEye 20/20MPI – Commercial IR3 Flame Detector (20/20-MPI-R)

Spectrex SharpEye 20/20MI - Mini Triple IR (IR3) Flame Detector (20/20-MI-1-1-F)

Ziton Dual IR in Zinc Alloy Housing (FF742)

The FF742 is a IR² flame detector in a die-cast zinc alloy housing. IR² models have execellent response to flame while providing immunity to extraneous sources. New micro-processor technology makes the detectors independent of flame intensity enabling it to operate through smoke, a layer of oil, dust, or water vapor. A high and low sensitivity setting according to EN54-10 is provided.

Installer and maintenance friendly

The units can be wired as conventional 2 wire, 4-20 mA, or relay contacts (fire, fault and pre alarm) in latching or non-latching operation. Remote test inputs are available to activate self-test.

A stainless steel adjustable bracket and weather shield is also available.

The units are tolerant to vibration, and wind does not affect the performance. The IR² unit has excellent tolerance to detector window contamination and can detect flame through glass windows.

A flame sensor test unit is available for accurate testing of the detectors.

Reducing false alarms

Most IR flame sensors respond to 4.3µm light, emitted by hydrocarbon flames. By responding to 1.0 to 2.7µm light emitted by every fire, all flickering flames can be detected. Gas fires not visible to the naked eye e.g. hydrogen may also be detected.

The IR² detectors, responding to adjacent IR wavelengths, enable it to discriminate between flames and spurious sources of IR radiation.

The combination of filters and signal processing allows the sensor to be used without risk of false alarms in difficult situations characterised by factors such as flickering sunlight.

Key Features

  • Dual IR detector
  • High specification units for critical applications
  • IP65 Housing
  • Low current consumption
  • 2 Wire, 4 - 20 mA and relay operation
  • Latching and non latching operation
  • High / Low sensitivity setting
  • Tolerance to detector window contamination
  • Remote self test facility
  • Microprocessor controlled
  • Immunity to false sources (arc welding, lightning and static)
  • Conforms to EN54: Part 10

Have you got a question about this product?

Email us or Call Us on +44 (0)1254 207532

Related Products