Linear heat detection clips & fixings come in different variants; use a suitable clip for whatever you are trying to fix the cable to. In accordance with BS5389 pt1 2002, LHDC should be spaced no more than 5.3m away from any zone boundary or wall and no more than 10.6m between adjacent runs. Additionally, LHDC should be installed such that it is between 25mm and 150mm from the ceiling.
If you can’t find what you’re looking for or want to know more about the different clips & fixings we stock & distribute, please Contact Us or give us a call on +44 (0)1254 207532 and a member of the team will be happy to assist.
Linear heat detection clips & fixings come in different variants; use a suitable clip for whatever you are trying to fix the cable to. In accordance with BS5389 pt1 2002, LHDC should be spaced no more than 5.3m away from any zone boundary or wall and no more than 10.6m between adjacent runs. Additionally, LHDC should be installed such that it is between 25mm and 150mm from the ceiling.