Lexicomm ViLX-228-0 Evacuation Voice Communication Master Station
- Part Number: ViLX-228-0
- Categories: EVC Controllers (Evacuation Voice Communication / Disabled Refuge System / PAVA)
- £680.78 (£816.94 inc VAT)
Lexicomm ViLX-228-0 Evacuation Voice Communication Master Station
This ViLX-228-0 is a Lexicomm master station to be used as a repeater, and is supplied in a wall mount enclosure with space for batteries (2 x 12v 7AH VRSLA Not Supplied). Built in network allows for a master & slave system or can be connected as a local master station as part of a 64 panel Lexicomm Network system for larger network projects. 8x front panel buttons with PGB LEDs and 7 status LEDs, can be expanded to up to 8 lines using ViLX-LC2. This unit fully complies to BS5839 part 9 2011.
The Lexicomm ViLX-228 Master station can accept up to eight lines of outstation, (type A fixed phones, type B refuge hands free points, emergency assist call point or jack points in Far East and Middle East applications) as required. Lines auto identify by flashing Red for EVCS calls, Blue for assist calls or flashing Green for Connected calls as detailed in BS5839pt9:2011 Assist Calls can be acknowledged by pressing the zone key (as required by BS8300) and will return to alarm if not reset within two minutes.
The case is made from powder coated zintec, with a smoked perspex door covering the handset. 20mm cable knock-outs are provided for all necessary cables as well as space for the backup 12V 7AH VRSLA battery. The repeater station is microprocessor controlled, it has an identical appearance to a LX228 master station and can control a maximum of 8 lines. Lines auto identify by flashing Red for EVCS calls, Blue for assist calls or flashing Green for Connected calls as detailed in BS5839pt9:2011.
The ViLX228 has inbuilt networking allowing it to form one of the 64 panels on a Lexicomm network installation, or allowing a repeater using another ViLX228, where buildings have two points of control. Starting at two lines he ViLX228 is ideal for small buildings which are required to have an EVCS, but which have a limited number of outstations.
All Lexicomm Emergency Voice Communications Systems (EVCS) are designed to comply fully with the requirements of BS5839-9:2011 for use as a fire telephone system (FT), disabled refuge system (DRS) or as a combined system when both fire telephones and disabled refuge call points are required. An EVCS is a fixed, secure, bi-directional, full duplex voice communication system to assist fire fighters during emergencies in high rise buildings or large sites where radio communication cannot be guaranteed to work due to interference from the fire corona.
Key Features:
- Compact Design
- Fully Compliant to BS5839-9: 2011
- Integrated Assist Call and acknowledge meeting BS8300
- 1.5A EN54-4:A2 PSU
- Full Duplex operation
- Wall mount enclosure
- Lockable handset cover
- Expandable from 2 to 8 lines
- Inbuilt networking
Optional Stainless right hand fascia is available for the ViLX-228 and ViLX-TSM controllers, please choose from Drop-Down box.
Lexicomm - Master Station - Installation Guide (1.2MB)
Lexicomm - ViLX-228 - Datasheet (588.24KB)
Have you got a question about this product?
Email us or Call Us on +44 (0)1254 207532