DETECT-A-FIRE® (D-A-F) detectors are the "heart"
of many fire protection systems. The highly reliable D-A-F has been the
standard for over 75 years. The D-A-F is used for signaling overheat or fire
conditions. In most applications, the D-A-F provides the initial heat sensing
that is used to activate suppression systems using clean agent, CO2, inert
gases, wet or dry chemicals or water.
D-A-F detectors are widely accepted because they are
designed with rate compensation. This provides a unique advantage over both
fixed temperature and rate-of-rise types of detectors because the D-A-F
detector accurately senses the surrounding air temperature regardless of the
fire growth rate. At the pre-determined set point, the system is activated.
Fixed temperature detectors must be completely heated to alarm temperature and
therefore a lag in response time may occur with a fast rate fire. Rate-of-rise
devices, on the other hand, are triggered by the rate of increase in ambient
temperature and are subject to false alarms caused by harmless, transient
thermal gradients such as the rush of warm air from process ovens.
The key to the detector's sensitivity is in the design. The
outer shell is made of a rapidly expanding alloy which closely follows changes
in surrounding air temperature. The inner struts are made of a slower expanding
alloy. Designed to resist thermal energy absorption and sealed inside the
shell, the struts follow temperature changes more slowly. A slow rate fire will
heat the shell and struts together. At the "set point", the detector
will trigger, actuating the alarm or releasing the extinguishant.
A transient rush of warm air up to 40°F/min. may expand the
shell, while not triggering the detector. By ignoring transient warm air
excursions, the D-A-F detector virtually eliminates false alarms prevalent with
rate-of-rise devices. If a fast rate fire starts, the shell will expand
rapidly. The struts will close, actuating the alarm and/or releasing the agent.
The faster the fire rate of growth, the sooner the D-A-F detector will react.
Key Features:
- Repeatable - self-restoring, nothing to replace, testable
- Versatile - various temperature settings available
- Durable - long-lasting stainless-steel shell
- Economical - wide spacings reduce installation costs
- Internal contact area hermetically sealed in stainless steel shell