ORB-HT-51146-APO Apollo Orbis I.S. A1R Heat Detector with Flashing LED
- Part Number: ORB-HT-51146-APO
- Categories: Detection (Conventional)
Please note: this product is now obsolete, the recommended replacement is the Apollo ORB-HT-51145-APO Orbis A1R I.S. Heat Detector.
ORB-HT-51146-APO Apollo Orbis I.S. A1R Heat Detector with Flashing LED
The Orbis IS Heat Detector monitors temperature by using a single thermistor network which provides a voltage output proportional to the external air temperature. The Orbis IS range incorporates seven heat detector classes to suit a wide range of operating conditions.
Operation:
Orbis I.S. heat detectors have an open-web casing which allows air to flow freely across a thermistor which measures the air temperature every 2 seconds. A microprocessor stores the temperature and compares them with per-set values to determine whether a fixed upper limit - the alarm limit - has been reached. In the case of rate-of-rise detectors the microprocessor uses algorithms to determine how fast the temperature is increasing.
Static heat detectors respond only when a fixed temperature has been reached. Rate-of-rise detectors have a fixed upper limit but they also measure the rate of increase in temperature. A fire might thus be detected at an earlier stage then with a static detector so that a rate-of-rise detector is to be preferred to a static heat detector unless sharp increases of heat are part of the normal environment in the area protected by the heat detector.
Key Features:
- Can be used for applications where smoke detectors are unsuitable
- Ideal for environments that are dirty or smoky under normal conditions
- Reduced incidences of false alarms
- Increased reliability of detection