Categories

Site Links

  • Apollo 45681-705APO Cat O. XP95 Sounder VAD Base with Isolator

Apollo 45681-705APO Cat O. XP95 Sounder VAD Base with Isolator

Apollo 45681-705APO Cat O. XP95 Sounder VAD Base with Isolator
  • £60.62 (£72.74 inc VAT)
Qty 5+
Prices £58.29
Inc VAT £69.95

Apollo 45681-705APO Cat O. XP95 Sounder VAD Base with Isolator

The XP95 Sounder VAD Base is a loop-powered sounder and EN 54-23 approved VAD combined with a standard intelligent mounting base. It is used to signal a fire alarm in enclosed areas.

You can perform a ‘Self Test’ this is an important safety feature which has been incorporated into the Sounder VAD Bases: when it is switched on it tests itself by checking the actual sound output and flash operation.

There are 3 possible outcomes from the test, if the transmitter reads:

  • A value of 1 (=Sounder fault) this means there was no sound detected in 5 seconds of the sounder being switched on.
  • A value of 2 (=VAD fault) means there is no current being drawn by the LED’s.
  • A value of 3 (=Sounder and VAD fault) where neither of the above elements are operating correctly.

If no sound is detected within 5 seconds of the Sounder VAD Bases being switched on it will transmit an analogue value of 1 (= sounder fault) when it is next polled.

This feature can also be used during commissioning or periodical maintenance testing. Simply activate the Sounder VAD for at least 5 seconds and check the control panel for a fault signal. If none is received, the Sounder VAD Base is working properly.

Key Features:

  • EN54-23 approved
  • Flash rate of 0.5Hz
  • Synchronisation of 'alert' and 'evacuate' tones 
  • Synchronisation of visual indicator flash
  • Individual and group addressing
  • Unique acoustic and VAD self-test
  • Built in isolator


Have you got a question about this product?

Email us or Call Us on +44 (0)1254 207532