Apollo 55000-812APO XP95 DIN-RAIL Zone Monitor with Isolator
- Part Number: 55000-812APO
- Categories: Ancillary (Addressable Fire Alarm Equipment)
- £70.46 (£84.55 inc VAT)
| Qty | 10+ |
|---|---|
| Prices | £67.75 |
| Inc VAT | £81.30 |
Please note: This product is currently on an extended lead time due to a component shortage. Please contact us for further information.
Apollo 55000-812APO XP95 DIN-RAIL Zone Monitor with Isolator
The DIN-Rail Zone Monitor with Isolator powers and controls a zone of up to 20 Apollo Series 65 or Orbis fire detectors in a Discovery or XP95 loop.
Operation:
The DIN–Rail Zone Monitor is factory preset to return an analogue value of 16 when all detectors on the zone are in the quiescent state and 64 when a detector changes to the alarm state. The unit latches in the alarm state. A 5.1k end-of-line resistor is used to monitor cables for open and short-circuit faults. Alternatively, an active end-of-line monitor may be used in conjunction with diode bases and a capacitor of up to 50uF fitted at the unit wiring terminals. In either case an analogue value of 4 is transmitted during open or short-circuit faults.
The DIN–Rail Zone Monitor is fitted with a bi-directional short-circuit isolator and will be unaffected by loop short-circuits on either loop input or output. For IS applications use DIN-Rail IS Zone Monitor, part number 55000-798.
Key Features:
- Loop-powered
- Visible short-circuit and alarm
- LEDs Built-in Isolator
Apollo Zone Monitor - Data Sheet (763.25KB)
Apollo Zone Monitor - Installation Manual (289.68KB)
Short Circuit Isolator - Information Guide (292.46KB)