CB200 1, 2, 4 and 8 Zone Conventional Control Panels
The CB200 conventional panel may be supplied in 1, 2, 4 and 8 zone formats. It complies with the requirements of EN54 Part 2. All zones and alarm circuits are monitored for open and short circuit fault conditions with detector removal facility also provided as standard.
The cabinet will house 2 x 12V 2.1AH S.L.A. batteries wired in series, which will sustain an 8 zone panel for up to 24 hours. All panels have a zone 1 non-latch facility to enable panel interlinking without "lock-up" occurring. The class change input enables the alarm circuits to operate without panel indication or panel latching.
The cabinet back box houses only the transformer, thus providing a virtually empty enclosure for first fix installation. A steel gland plate, removable plastic grommets and ample space are designed to assist with cable termination. A slide-in insert is included for a clear zone identification. The surface mount electronics motherboard is fitted and terminated after first fix installation. Finally a terminal cover completes the panel installation.
The 4 & 8 zone panels will accomodate up to 3 repeater panels, which are connected by a shielded 2 core data cable where the repeater panels are powered locally, or an additional 2 core may be run from the panel for power (max 1 repeater may be powered from the panel).
Features
- Built in detector removal indication facility
- From 1 to 8 zones
- 4 Alarm circuits on 4-8 zone panels
- Conforms to the requirements of EN54-2
- User friendly access code
- one-man test facillity
- Non-latching zone feature
- Class change input
- Earth fault monitoring
- Fully functional repeater available (4 & 8 zone panels only)
- Removable cable entry grommets
- User friendly controls
- Surface or semi-flush mounting as standard
- Ample termination space
- Flame restant polycarbonate enclosure
- Log book and manual supplied
- Complies with SMC and LVD directives
Download CB200SL Data Sheet acornfiresecurity.pdf
Download CB200 Installation and Commissioning Manual acornfiresecurity.pdf
Download CB200 Application Guide acornfiresecurity.pdf
Contact us about this product