BF367 AUXILIARY DEVICE ISOLATOR
The BF367 allows a +24V d.c. output from a fire panel to be remotely isolated to prevent external equipment (such as remote signalling, plant shutdown, etc.) from operating - a particularly useful function during routine
maintenance as it safeguards against the inadvertent triggering of auxiliary
equipment.The unit incorporates an isolating keyswitch and amber LED. The switch circuit has been designed so that if monitoring is used on the +24V d.c. output being controlled, a fault condition will show at the fire panel when
the BF367's keyswitch is ‘ISOLATED'. Can be mounted on a 25mm flush or surface UK single gang back box.
SPECIFICATION
Required current for fault LED 10mA @ 27.6V d.c.
Switch ratings Non-switching current rating 5A Max.
Switching Resistive load 3A @ 30V d.c.
Switching Inductive load 1.5A @ 30V d.c.
Switch material Silver plated brass.
Dimensions (WxHxD) / Weight 86 x 86 x 38mm / 109g (packed)
Download Conventional Ancillaries acornfiresecurity.com.pdf